Technical FAQs

Ask a Question

Can circuit breakers be reverse-fed or back-fed? A compiled list included.

Product Line:
Circuit Breakers

Electrical Distribution Equipment

Any circuit breaker that does NOT have Line and Load (or + and - on DC breakers) identifying markings may be reverse fed. This includes all Square D industrial thermal-magnetic and electronic trip circuit breakers.  See the compiled list below:

Breakers that can be back fed and exceptions (This is a work in process list, it is probably not inclusive and does not yet include legacy breakers):
  • HOM (Excludes those with suffix GFI, EPD, AFI, CAFI and DF.)
  • QO and QOB (Excludes those with suffix GFI, EPD, EPE, AFI, CAFI and DF.)
  • QOU
  • Multi 9 products (Excludes the products rated 125VDC, and 250-500Vdc. Also excludes ID Residual current switches, GFP, DPN VIGI and Vigi modules.)
  • E frame for NF panel (Excludes those with suffix EPD.)
  • Powerpact H, J and L frame (Excludes those with T or R suffix, which are breakers with replaceable trip units. Also excludes those with Fxx suffix, which are "frame only" sold without terminations or trip unit.)
  • Powerpact Q frame
  • Powerpact M, P and R frame
  • Masterpact NT and NW (Excludes Masterpact DC rated breakers)
  • SEF and SED Circuit Breakers, with or without ground fault
  • NOTE: Any Legacy or Powerpact breakers with GFM and ELM module attached cannot be reverse fed.
Was this helpful?
What can we do to improve the information ?