How Many Modules Can be Added to the 9421V1 or 9421V2 Metallic Enclosed Switches?

Issue:
Needs to know if we can add 2 blocks inside the enclosed switch

Product Line:
Disconnect Switches

Environment:
Vario Enclosed Switches

Resolution:
One 2 pole aux contact module can be added on each side.   2 power pole modules can be added to either side.   Or a combination of 1 power pole and 1 aux contact module can be added to the right side.   See attached table from catalog.