What are the amperage ratings of a 9013G pressure switch?

Issue:     
Will a 9013G switch handle 20A at 230V 1phase and 3HP?

Product Line:
Pressure Switches

Environment:
9013 Pressure Switches

Cause:
Will a 9013G switch handle 20A at 230V 1phase and 3HP? 

Resolution:
The 9013G are not current rated devices. They are HP rated devices only. To use on 3 phase circuits, wire 2 phases through the 2 poles of the switch and direct wire the third phase to one of the motor leads. This makes the lead live when the pressure switch is OFF.

 