What are the replacement test kit cables for the FFTK (S33595) and the HHTK (S33594)?

Issue:
Replacement cables for test kits S33595 and S33594

Product Line:
Circuit Breakers

Environment:
Applies to these test kits:
S33595 Full Function Test Kit (FFTK)
S33594 Hand Held Test Kit (HHTK)

Resolution:
The FFTK and HHTK have 2 different cables for testing breakers.

S48907
The 7 pin test cable is catalog number S48907. It is used for testing Powerpact M, P, R frame breakers and Masterpact NT and NW breakers with these trip units:
ET 1.0M, ET 1.0I, ET1.0
Micrologic 2.0, 3.0, 5.0
Micrologic 2.0A, 3.0A, 5.0A, 7.0A
Micrologic 5.0P, 5.0H, 7.0P, 7.0H
Micrologic 6.0A, 6.0P, 6.0H
NOTE: There is a label on the cable that shows number 5100512198, and another label shows 33590. Neither of these should be used to order a replacement cable. The correct number is S48907.

S48908
The 2 pin test cable is catalog number S48908. It is used for testing STR trip units on Compact NS and Powerpact D frame breakers with these trip units:
STR22ME, STR22GE, STR22SE, STR23SE, STR23SP, STR43ME, STR53UP, STR53UE
 