What is included in alternate lug kit #: 32510 for use with DJM circuit breakers?

Kit includes (3) 2-barrel lugs for (2) #2-350 Al/Cu or (2) #2-500 Al per lug.
The 32510 lug contains two wire binding screw lengths.  As longer set of screws 24.5mm for smaller cable the #2 AWG minimum.  And a shorter set of screws 18mm for larger cable the #4/0 minimum.