What is the standard terminal lug data and are their alternate lugs for the EZM1800TB Series M01?

Issue:
Product Design Features

Product Line:  
EZ Metering Equipment

Environment:  
Lug data

Resolution:
The Standard terminal lug data (or wire range) for this device is:
The line and neutral main lugs will accept (4) 3/0 AWG to 500 kcmil Al/Cu conductors and Ground lug will accept (1) # 6 - 300kcmil Al/Cu wire.

The Alternate terminal lug data (or wire range) for this device is:
1) To accept (2) 1/0 AWG to 600 kcmil Al/Cu OR (4) 1/0 AWG to 250 kcmil Al/Cu conductors per phase and neutral order (2) MMLK250 lug kits. Each MMLK250 Lug kit contains (3) 2 barrel lugs for terminating (1) 600 kcmil or (2) 250 kcmil Max. conductors PER lug. Each Phase bar and neutral will accept two lugs.

2) To accept (2) 1/0 AWG to 750 kcmil Al/Cu conductors per phase and neutral, order lug kit part number 7329696650. This kit includes Phase and Neutral, L-Shaped mounting pads, each pad contains two lugs to accept (1)1/0 AWG - 750 kcmil AL/CU wire per Lug. The kit is also supplied with all the necessary mounting hardware and phase insulators.
 
 