What is the largest branch circuit breaker that can be installed into a QO 3 Phase Load Center?

Issue:
Max amperage branch breaker that can be installed in 3-phase QO load center

Product Line:
QO Load Center

Environment:
QO Load Centers

Cause:
Application

Resolution:
QO 1 pole breaker maximum is 70A
QO 2 pole breaker maximum is 125A
QO 3 pole breaker maximum is 100A
NOTE: The maximum branch breaker cannot exceed the mains rating of the QO Load Center. 


 