Technical FAQs

Ask a Question

Do the Micrologic trip unit protective relay functions have ANSI certification?

Issue:

Micrologic trip unit protective relay functions have ANSI certification

Product Line: 

NEMA AND DEFINITE PURPOSE CONTACTORS AND STARTERS

Environment:

North American Products


Resolution:

No. Our advanced protection functions in the Micrologic P/H trip units are not certified to ANSI C37.2 which requires a 30A output that the M6C cannot deliver.
The basic trip unit functions (overload, short circuit, instantaneous & ground fault) were qualified to ANSI C37.17 and C37.50 as part of the NW qualification.
Was this helpful?
What can we do to improve the information ?