What replaces the FDA frame breaker?

Issue:
What other breakers can be used in place of the obsolete, I-line,  Powerpact F frame breaker?

Product Line:
Circuit Breaker 

Environment:
I-line breakers FDA FGA FJA

Resolution:
You can replace with FA, FH powerpact B such as BDA, BGA or BJA or H frame breakers such as HDA HGA or HJA.  Current 3P breaker offering will require 4.5" of mounting space where the Powerpact F frame only took up 3".  Customer will need to make sure he has additional space for mounting new 3P breakers. 


 