What is the wire binding screw torque value for the MA/MH breaker lug?

Issue:
Wire binding screw for MA/MG circuit breaker lugs

Product Line:
Molded Case Circuit Breaker

Environment:
Legacy M-frame Circuit breaker lugs

Resolution:
Applies to the following lugs: AL800MA7 AL900MA AL900MAT AL1000MA AL1000MAT CU1000MA
The wire binding screw torque is 300 lb-in (34 NM)
 