Is there a way to test ground fault on a Masterpact NW or NT breaker and not trip the breaker?

Issue:
Ground fault test in Masterpact breaker
 
Product Line:
Air Circuit Breaker
 
Environment:
Masterpact NW and NT
 
Resolution:
NO. Primary injection test, use of the Full Function Test Kit, and GF test button on the front of the trip unit will all trip the breaker.