On a Masterpact NT/NW the charge and discharge button normally shows either charged or discharged. What does the ``OK`` with a line through it indication mean?

Issue:
On a MasterPact NT NW the charge and discharge button normally shows either charged or discharged.  What does the ``OK`` with a line through it indication mean?

Product Line:
Masterpact NT NW

Environment:
Manual or electrically operated

Resolution:
When the charge indicator shows "Charge Not OK", the breaker contacts are open and the charging spring is inhibited for some reason. This reason must be cleared before the breaker can be closed. The status indicator may indicate this for multiple reasons:

UVR not energized.
Shunt Trip that is energized.
Padlock attachment pulled out or not aligned (try loosening the cover or taking it off to realign the attachment).
Push to Close button is partially depressed.