What size wires will terminate in the Powerpact J frame breaker?

Product Line:
Electrical Distribution Equipment

Environment:
PowerPact J-frame Circuit Breakers

Resolution:
The wire ranges are:

150-175 A ; #4-4/0 AWG Al or Cu; Lug kit Cat. # AL175JD [includes 3 lugs]
200-250 A ; #3/0-350 kcmil Al or Cu; Lug kit Cat. # AL250JD [includes 3 lugs] (optional on 150-175 A)