What is the 800 ampere main breaker used in an I-Line panel interior, catalog number HCP36868M? Can this be changed to a 600A breaker?

Issue:
Replacement main

Product Line:
Panelboards

Environment:
I-Line

Cause:
Maintenance , conversion

Resolution:
The factory installed main breaker in the HCP36868M is an MGP36800. Customer can install an MGP36600 breaker to make the panel 600 ampere.


 