Can Class T fuses be installed in Heavy Duty Safety Switches?

Issue:
Application

Product Line:
Heavy Duty Safety Switch

Environment:
Fusible Switches

Cause:
Selection

Resolution:
Class T provisions are not an available feature in the Heavy Duty safety switch product line. If the applied voltage is 240Vac maximum, consider using a General Duty safety switch. We do offer General Duty switches suitable for using ONLY 300Vac Class T fuses in 400A, 600A and 800A, NEMA Type 1 and 3R, 3 Phase/4Wire. We have no offering for using Class T fuses on voltage systems over 240Vac.