In what hazardous locations, as defined by the NEC, is the H100XFA suitable for use?

Issue:
What hazardous locations can the H100XFA be applied?

Product Line:
Heavy Duty Safety Switch

Environment:
Special Applications for Heavy Duty Safety Switches

Resolution:
The H100XFA is suitable for use in Hazardous Locations defined by the National Electrical Code (NEC) as Class I, Groups C & D, Divisions 1 & 2; Class II, Groups E, F & G, Divisions 1 & 2; or Class III, Divisions 1 & 2. The device will be marked for Class and Group, but is not required to be marked for Division per NEC 2005 Article 500.8(B)(2) FPN (Fine Print Note).