Are MagGard Motor Circuit Protectors (MCP)s UL489 listed?

Issue:
Are motor circuit protectors, or Mag Gard Breakers UL 489 listed?

Product Line:
Circuit Breakers

Environment:
Application

Resolution:
Motor Circuit Protectors do not have a UL 489 listing per se, but are a UL recognized component for use in a motor control application in conjunction with a thermal overload component.


 