What is the maximum height for a housekeeping pad for 25KV metalclad switchgear to insure that the pad will not interfere with the breaker lift truck.

Issue:
What is the maximum height for a housekeeping pad for 25KV metalclad switchgear to insure that the pad will not interfere with the breaker lift truck. 
Product Line:
HVL.

Environment:
Products sold in the United States.

Cause:
Application.

Resolution:
The acceptable dimensions are 6`` in front of lineup and 6`` high. These dimensions still allow the lift truck to be operational. The maximum allowable pad is 7`` from the front of gear and 7`` high. Any higher pad will interfere with the removal of the breaker from upper cell.


 