Can the EDB, EGB, EJB type breakers be used on 400 Hz systems?

Product Line:
Circuit Breakers

Environment:
Electrical Distribution

Resolution:
Yes. The thermal de-rating for all amperages is 0.97. The magnetic rerating multiplier is 2.6. The interrupting rating is 10% of the 60 Hz interupting rating.
NOTE: NOT UL LISTED
 