Is an auxiliary switch available on both the QO and QOB circuit breakers?

Issue:
How to get auxillary switch in a QO and QOB breaker?
 
Product Line:
Miniature Circuit breaker
 
Environment:
QO and QOB Circuit breaker
 
Resolution:
Yes, most QO and QOB circuit breakers can be provided with an auxiliary switch accessory. Use suffix 1200 for an auxiliary switch which is open when the breaker contacts are open (1a), or suffix 1201 for an auxiliary switch which is closed when the breaker is open (1b). Suffix 1212 for 1a1b contacts is NOT valid with QO and QOB circuit breaker.

QO arc fault breakers, as well as the QO2150, QO2175, and QO2200, are not available with an auxiliary switch accessory.
QOB2150VH, QOB3110VH, QOB3125VH, and QOB3150VH are not available with an auxiliary switch accessory.