What is the location of the 5th jaw on the EZM, EZMH, EZMK, EZML or EZMR branch device and what 5th jaw is used if needed?

Issue:
Application

Product Line:
Multi Metering

Cause:
Application

Resolution:
NOTE:
ALL Sockets include 5th Jaw factory installed except the EZM11____ devices, they are all 4-jaw meter sockets
It will depend on the device catalog number.
1) EZM prefix units that are supplied with 5th jaws have the 5th jaw factory installed in the 9 o'clock position. When needed, the 5th jaw can be moved in the field to either the 3 or 6 o'clock position, depending upon local utility requirements.
2) EZMH, EZML and EZMR prefix units(1-phase out) are all supplied with 5th jaws installed in the 9 o'clock position. When needed, the 5th jaw can be moved in the field to either the 3 or 6 o'clock position, depending upon local utility requirements.
3) EZML and EZMR prefix units(3-phase out) are supplied with the 5th jaws installed in the 6 o'clock position. When needed, the 5th jaw can be moved in the field to either the 3 or 9 o'clock position, depending upon local utility requirements.
-EZMK units are not supplied with 5th jaw. Contact 1-888-SQUARED for further information.

NOTE: If a 5th jaw is required the part number is 5J



 