How can input phase loss fault be disabled with the Altivar 58 drive?

Issue:
How can input phase loss fault be disabled with the Altivar 58 drive?

Product Line:
Altivar 58

Environment:
All

Cause:
N/A

Resolution:
Go to menu 6 (FLt - fault menu)
Set the IPL  parameter (Input Phase Loss) to no.
This will allow the drive to continue running without PHF fault if there is a loss of input phase voltage. This does not disable other faults in the drive.
See keypad programming manual for additional details.