Does Square D offer a 30mm 9001K control station rated for use in hazardous locations?

Issue:
What enclosures and operators to use for Class 1 Div 2?

Product Line:
30mm Push Buttons                    
   
Environment:

Type K and SK Electrical Components

Cause:
Determine is Schneider Electric has an control station to offer for this application.               

Resolution:                                                                 
Yes , but only for Class 1 Division 2 or Class II Division 2 Groups E & F.  Any Nema 4 & 13 enclosure ( ie. 9001KY** , KYSS** , SKY*** ) can be used,  if hermetically sealed contact blocks ( ie. 9001KA41 , 51 ) are used with 9001K or SK operators ( except potentiometers ) .
 