What is the wire range for the Powerpact R frame breaker with an RLTB kit?

Published date: 10 September 2019

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment

Resolution:
Lug kit # AL2500RK for the R frame breaker includes two lugs, and each will accept (1) 1/0 to 750 kcmil. A total of 8 lugs can be installed per terminal.
 