Where do I connect the Vn connection on the NCT of Powerpact P and R frames, as well as Masterpacts?

Issue:
Where does the Vn connection get made on the P and R-frame and Masterpact neutral current transformers?

Product Line:
Circuit Breakers

Resolution:
The Vn connection is used with a Power metering trip unit (5.0P or 6.0P) trip unit or Harmonic (5.0H or 6.0H) trip unit because they monitor voltage. In this case, wire Vn from the NCT to Vn on the breaker. The Vn connection is not used with ammeter trip unit (5.0A or 6.0A) because it only monitors current and not voltage.