What is the torque requirement for the lugs on a 400A main lug and neutral I-line panel?

Issue:
Torque specs for I-Line panel lug

Product Line:
Panelboards

Environment:
I-Line

Cause:
Installation and maintenance

Resolution:
For 3/8`` screw it is 340 in-lbs. For 1/2`` screw it is 450 in-lbs.


 