Can the Class 8538 Type S combination starters be supplied with DC control coils?

Issue:
Need to utilize DC control voltage in a Type S combination starter

Product Line:
NEMA and Definite Purpose Contactor and Starter

Environment:
NEMA combination starters

Resolution:
No, these starters use the Class 8536 Type S NEMA devices which are not available with DC control coils. You may use a DC controlled interposing relay and switch the contactor at line voltage.
 