What are the Coil Voltage Limits for the LC1K and LC2K Contactors?

Issue:
Information on the voltage tolerance on the LC1K and LC2K contactors

Product Line:
IEC Contactors

Environment:
Type K Contactors

Resolution:
For operation between 80 to 115 percent of the rated voltage. Exception: LC1K16* is 85 to 115 percent.
For drop-out 20 percent or less of the rated voltage.