Can the HQO****** distribution panel for I-Line panels accommodate a QO120GFI breaker ?

Issue:
Can the HQO****** distribution panel for I-Line panels accept QO-GFI and QO-EPD breakers?

Product Line:
I Line panelboard

Environment:
Application 

Cause:
Clarification

Resolution:
Yes, 15-30a 1P, 2P and 3P QO GFIs can be installed into the distribution center. But the HQO distribution load center has only (6) 1 pole space provisions, so it can accept (6) 1 pole GFIs, (3) 2 pole GFIs and (2) 3 GFIs.

30A is the maximum amperage that can be installed.  