How can ground fault protection be added to the C60 Multi 9 circuit breakers?

Issue:  
GFP and RCCB availability for Multi 9 breakers and supplementary protectors

Product Line:  
DIN Rail Mounted Circuit Breakers

Environment:  
Multi 9 Devices

Resolution: 
To add ground fault protection to Multi 9 circuit breakers, a UL 1053 listed Ground Fault Protector (GFP) or IEC 61008 listed Residual Current Circuit Breaker (RCCB) must be wired in series with the Multi 9 breaker or supplementary protector.  These devices offer equipment protection at 30 mA, 100 mA or 300 mA.  See current Multi 9 catalog here on the Schneider Electric website for available options.  