What main breaker does the SC12L200F use?

Issue:
Product Design Features

Product Line:
Combination Service Entrance Devices

Environment:
Main breaker

Cause:
Application

Resolution:
This meter main is designed as a Main Lug device to meet the Six Service Disconnect Rule per the Code, so it does not use a Single Main Breaker. The device will accept up to 6,  HOM, 2pole Service Disconnects up to  200amp maximum.



 