Is there information available on Test Kit part 43362, BU Mini test kit for ST and STR trip units?

Issue:
Is there information available on 43362?

Product Line:
Circuit Breakers

Resolution:
There are no printed instructions for this test kit.
For Instantaneous testing, set the switch to Im and plug the test cable in with the polarity indicated, matching the markings on the plug and the trip unit. For Ground Fault testing, move the switch to Ih and reverse the test plug.