Will a remote main series rated to the branch breakers installed in a main lug feed thru panelboard and to the branch breakers in the main lug panelboard that is being fed from the feed thru panelboard?

Issue:
Will a remote main series rated to the branch breakers installed in a main lug feed thru panelboard and to the branch breakers in the main lug panelboard that is being fed from the feed thru panelboard?

Product Line:
Panelboards.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
Yes, providing the remote main does have a series rating to the associated branch breakers in each panelboard.


 