What blank fillers are required in an I-Line panel when an LI breaker is replaced with a KI?

Issue:
What additional parts do I use to cover the extra space when replacing an LI style breaker with a KI style breaker?

Product Line:
I-line Panelboards

Resolution:
The following parts are required :

(1) HLW4BL (add on to the end of the KI)
(1) HNM1BL and (1) HLW1BL (will need two of each, but each part number comes with a kit of three)