What are the maximum torque specs for tightening the power and control connection screws on a LC1D ?

Product Line:
Tesys D line contactors
The power circuit tightening values are LC1D09-18 = 15 lb. in , LC1D32-38 = 23 lb. in. , LC1D40-65 = 45 lb. in and LC1D80-150 = 100 lb. in . The control circuit values are 15 lb. in for all sizes