Does Schneider Electric / Square D offer NEMA Type 7 or NEMA Type 9 disconnects for use in hazardous environments?

Issue:
Availability of Nema 7 and Nema 9 Switches or Circuit Breakers

Product Line:
Safety Switches and Circuit Breakers

Cause:
Selection

Resolution:
Square D does not offer a Visible-Blade type of General Duty, Heavy Duty, or Double Throw disconnect in Hazardous Location (NEMA 7 or NEMA 9) enclosures. For non-fusible applications, enclosed automatic molded case switches are available. Devices 60 ampere and 100 ampere are cULus Listed. Devices rated 225 ampere are not listed due to limited wire bending space. There is no offering over 225 ampere.  Where overcurrent and short circuit protection is required, Hazardous Location enclosures for molded case circuit breakers are available.  

Refer to the latest Schneider Electric Digest online for selection.