Can a single EZM Branch device contain both three phase and single phase meter sockets?

Issue:
EZM Applications

Product Line:
EZM Metering

Environment:
Both Single and three phase EZM metering

Cause:
Mixing singe and three phase is the same line-up.

Resolution:
A single EZM branch device CANNOT contain both single phase and three phase meter sockets. Also, a EZM Line-up that is Single Phase incoming and outgoing, CANNOT contain three phase branch units. BUT a EZM Line-up that is Three phase Incoming, can contain both three phase outgoing and single phase outgoing meter sockets, but the appropriate EZM branch devices are required. 