What is the Short Circuit Current Rating(SCCR) of General Duty Safety Switches?

Issue:
Product Design Features

Product Line:
General Duty Safety Switches

Environment:
Short Circuit Current Ratings(SCCR)

Cause:
Application

Resolution:

The SCCR for General Duty switches is dependent upon the type of fuses used in or protecting the switch. Using Class H or K fuses, SCCR is 10,000 AIC MAX. Using Class R, J, T or L fuses, SCCR is 100,000 AIC MAX.


 