Can the HOM2150BB, HOM2175BB or HOM2200BB be used as a main breaker in Any CSED device, for example the RC816D200CH?

Issue:
Product Design Features

Product Line:
Combination Service Entrance Devices

Environment:
Main Breakers

Cause:
Application and availability

Resolution:
NO. The HOM2150BB, HOM2175BB and HOM2200BB are Homeline Branch breakers and NOT main breakers. The main breaker for the RC816D200CH is a HOM2200 and is physically different than the branch breakers. The HOM-BB branch breakers cannot be used as a replacement main breaker.