Technical FAQs

Ask a Question

What is the coil tolerance for Tesys D-line contactors LC1D40 - LC1D115?

Issue:
What is the coil tolerance for Tesys D-line contactors LC1D40 - LC1D115?

Product Line:
D line contactors.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
AC single frequency coils for LC1D40 to D115: (-15% +10%)
AC dual frequency coils for LC1D40 to D80: (-15% / +10%)
AC dual frequency coils for LC1D95 to D115: (-20% / +15%)
DC standard coils for LC1D or LP1D40 to D80: (-15% / + 10%)
DC standard coils for LC1D115 & D150: (-25% / +20%)
DC wide range coils for LC1D or LP1D40 to D80: (-25% / +20%)


 
Was this helpful?
What can we do to improve the information ?