When an 8536 single phase starter is ordered, does it come with a 3-phase overload relay and a jumper strap kit from the factory?

Issue:
How will an 8536 Single Phase Starter looks like

Product Line: 
NEMA and Definite Purpose Contactor and Starer

Environment:
8536 Magnetic Starter 
 
Resolution:
It will have the center pole hardware on the contactor and overload removed and a single jumper strap is installed in the third leg of the overload relay. The customer will need to install one thermal unit sized per motor full load amperage.