What is the power terminal lug data for the LC1D18, LC1D25, LC1DT40, and LC1DT32 contactor?

Issue:
What size conductors to the LC1D18-DT32 contactors accept? 

Product Line:
TeSys D Contactors

Environment:
US Product

Cause:
Product Selection

Resolution:
For contactors with screw clamp terminals:
stranded cable w/o cable end : One or Two #18-8 AWG per terminal.
stranded cable w/cable end: One #18-3 AWG per terminal or Two #18-10 AWG per terminal.
solid cable: One or Two #18-8 AWG per terminal.


 