Is the 9999SA2 start stop pushbutton kit momentary or maintained ?

Issue:
9999SA2 operation

Product Line:
Cover-Mounted Control Units

Environment:
North American Products

Resolution:
They are momentary contacts that are meant to be wired into the holding circuit of the starter.