What is the shunt trip or under voltage trip clearing time for the PowerPact H- J- & L- circuit breakers?

Issue:
What is the clearing time for shunt trip or UVR? 

Product Line:
Molded Case Circuit Breaker Accessory

Environment:
Shunt Trip (MX) & Undervoltage (MN) accessories

Resolution:
AC or DC Undervoltage release, With no intentional delay it is less than 50 milliseconds.

Note: To know how does a shunt trip work to trip a circuit breaker? click here
          To know how does an under voltage accessory trip a circuit breaker? click here