Are I-line interiors provided as standard with copper or aluminum bus?

 
Answer
Issue:
Bus bar material type

Product Line:
Panelboards

Environment:
I-Line

Cause:
Interior Content

Resolution:
As RTI (Ready to Install), the HCM and HCP construction interiors of 600A and less, are provided as standard with aluminum bus, with interiors of 800A and greater , being provided with copper bus.
The HCP-SU interiors, which are rated 800A, and HCR-U interiors, which are rated 1200A, are provided as standard with copper bussing.
 



 