What are the acceptable wire sizes for the Class 8910 Type DPA definite purpose contactors?

Issue:
What are the acceptable wire sizes for the Class 8910 Type DPA definite purpose contactors?

Product Line:
Definite Purpose Contactors

Environment:
Products sold and used in the United States

Resolution:
As listed below based on device used:

Class 8910 Type DPA12, DPA13, DPA14, DPA22 DPA23, DPA24, DPA32, DPA33, DPA34 will accept 14 awg to 8 awg solid or stranded coper wire only.

Class 8910 Type DPA42, DPA43, DPA44 will accept 14 awg to 6 awg solid or stranded coper wire only.

Class 8910 Type DPA52, DPA53, DPA62, DPA63 will accept 14 awg to 2 awg solid or stranded coper wire only.

Class 8910 Type DPA72, DPA73, DPA92, DPA93, DPA122, DPA123 will accept 14 awg to 1/0 solid or stranded coper wire only.

Class 8910 Type SYD138 & SYD230 will accept 8 awg to 350 MCM solid or stranded coper wire only.

Class 8910 Type SYD368 will accept 8 awg to 500 MCM solid or stranded coper wire only.





 