What is the instantaneous Hold and Trip ratings for EDB, EGB and EJB breakers?

Issue:
What is the instantaneous rating for E-Frame Breakers?

Product Line:
Circuit Breakers

Environment:
E-Frame Circuit Breakers

Resolution:
For 15A through 30A EDB, EGB and EJB E-Frame breakers:
Hold Rating: 270A
Trip Rating: 875A
For 35A through 70A EDB, EGB and EJB E-Frame breakers:
Hold Rating: 630A
Trip Rating: 1800A
For 80A through 125A EDB, EGB and EJB E-Frame breakers:
Hold Rating: 1000A
Trip Rating : 2300A