What is the torque value for the wire binding screw on a QMB366W?

Issue:
What is the torque value for the wire binding screw on a QMB366W?

Product Line:
QMB Panelboards

Environment:
Installation

Cause:
Maintenance

Resolution:
Lug wire binding screws should be torqued to 375 inch pounds.  Each switch contains torque charts for the switch connections. 


 