What unit is the current replacement for the obsolete VSD07, ATV11 or ATV16 drives?

Is there a cross reference for AC Drives VSD07, ATV11 or ATV16

Product Line: 
AC Drives

VSD07, ATV11, ATV16

Product Evolution

Check the voltage and amperage ratings.
For most of the 120, 208 & 230 VAC single or three phase input ratings use the ATV12 with the same or higher Amperage rating.
For the 460 VAC ratings select from the ATV312 drives.
For all units, compare dimensions to be sure that the replacement drive will meet the requirements. 
Wiring, mounting and programming will be different.
The local Product Application Engineer (contacted by distributor) may need to be consulted to determine whether configuration changes need to be made to existing wiring etc when implementing a replacement drive. 

Check the current Digest for actual part numbers, or use the online selector tool: