How many Sub-Feed Circuit Breakers can be added to an NQOD Panelboard?

Issue:
Is it possible to put 2 or more sub feed breakers in an NQOD panel?

Product Line:
Panelboards

Environment:
NQOD Panelboards

Resolution
For the NQOD 225Amp Main Lug or 250Amp Main circuit breaker, only 1 sub-feed breaker can be installed. While 2 sub-feed breakers for a placed in a 400Amp to 600Amp panel..

NOTE: SUB-FEED BREAKERS ON NQOD PANELS ARE AVAILABLE AS FACTORY ASSEMBLED ONLY.  The NQOD panelboard product line is now obsolete, replaced
by the NQ panelboards.  